HP (Hewlett-Packard) UPS R1500 GENERATION 2 Power Supply User Manual


 
Troubleshooting 33
Troubleshooting
LED and audible alarm troubleshooting
Condition
Power
On LED
(green)
On
Battery
LED
(yellow)
Overloa
d LED
(red)
General
Alarm LED
(red)
Audible alarm
Can
alarm be
silenced
("Silencin
g an
audible
alarm"
on page
24)?
UPS operating from
utility
On Off Off Off No audible alarm N/A
Buck mode (high
input voltage)
On Off Off Off No audible alarm N/A
Boost mode (low
input voltage)
On Off Off Off No audible alarm N/A
Over temperature
condition
On On Off Flashing OnContinuous No
Battery test failure Off On Off Flashing OnContinuous Yes
Fan failure On Off Off Flashing OnContinuous No
Output short circuit On On On Flashing OnContinuous No
Power up failure
from a DC start
Low battery (no
utility power)
Flashing Flashing Flashing Flashing
On3 beeps/10
seconds
No
Low battery (no
utility power)
Off Flashing Off Off
On2 second
beep
No
OnlineUPS power
capacity exceeded
On Off On Off
On1 second
beep
No
Overload timeout Off Off On Flashing OnContinuous No
On batteryInput
voltage is out of
range
On On Off Off
On2 second
beep
Yes
On batteryNo
utility power
Off On Off Off
On4 second
beep
Yes
On battery—Battery
voltage condition
Flashing Off Off Flashing OnContinuous Yes
On battery
Overload condition
Off On On Off
On1 second
beep
No