Honeywell NETAXS-123 Network Hardware User Manual


 
Installing the NetAXS-123 Panels
Panel Components and Descriptions
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A 7
Caution: The system has not been verified for compliance with UL1076 Burglar Alarm units and
systems.
2.2 NetAXS-123 Access Control Unit
The NetAXS-123 panel is a one-door access control unit that you can supplement with an add-on
board that supports second and third doors. The following table shows the NetAXS-123 input/output
options:
Table 3: NetAXS-123 Input/Output Options
You can use the NetAXS-123 panel as a standalone panel with independent card and transaction
storage or, with a host software upgrade, as a fully monitored online access control device.
Panel inputs are capable of four state supervision: Normal, Alarm, Short and Cut. One input is used for
request to exit on each door and one input is used for door status on each door. Supervised inputs for
External Power Fail and Reader Tampers are supplied as well, and they can be used as additional
inputs when not required for their default purpose.
2.2.1 NetAXS-123 Add-On Board
The NetAXS-123 Add-On Board enables you to expand from one door to either two or three doors.
The board easily connects to the NetAXS-123 controller board (see the NetAXS-123 Add-On Board
Installation Guide (800-05787).
Board Readers Inputs/Outputs
Controller 1 door/2 readers 1 lock output
1 aux output
1 status input
1 Request to Exit
2 reader tamper/AUX
inputs
Add-On (1 Door) 1 door/2 readers 1 lock output
1 aux output
1 status input
1 Request to Exit
2 reader tamper/AUX
inputs
Add-On (2 Door) 2 doors/4 readers 2 lock outputs
2 aux outputs
2 status inputs
2 Request to Exits
4 readers tamper/AUX
inputs