IBM 42E Personal Computer User Manual


 
NetBAY Power Distribution Units 165
Line cords
The 2.5 m (8.2 ft) fixed line cord on the Rack PDU determines the connectivity of the
Rack PDU. The following table contains a list of the line cords that you can use with
the Rack PDU:
Power cables
The Rack PDU comes with three power cables, that you use to connect to other
M/PDU family devices, as listed in the following table:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 1.6 kg (3.5 lbs)
Operating temperatures 10°C35°C (50°F95°F) at 0914 m (03000 ft)
10°C32 °C (50°F90°F°) at 9142133 m (30007000 ft)
Operating humidity 880% (non-condensing)
Rated voltage 100120 V ac, 30 A, single-phase
200240 V ac, 30 A, single-phase
200240 V ac, 32 A, single-phase
200240 V ac, 30 A, single-phase
380415 V ac, 32 A, single-phase
Rated frequency 5060 Hz
Maximum power rating 4800-6000 VA
Power inlet One fixed line cord
Power outlets Three IEC 320-C19 outlets rated at 16 A (VDE) / 20 A
(UL/CSA)
Power Source Line cord rating Plug type
Line cord
part #
100-127 V ac, 30 A, single-phase 127 V, 30 A NEMA L5-30P 24P6846
200-240 V ac, 30 A, single-phase 250 V, 30 A NEMA L6-30P 24P6847
200-240 V ac, 32 A, single-phase 250 V, 32 A IEC 309-2P + Gnd 24P6848
200-240 V ac, 30 A, three-phase 250 V, 30 A NEMA L21-30P 24P6844
380-415 V ac, 32 A, three-phase 415 V, 32 A IEC 309-3P + N + Gnd 24P6845