IBM IBM UPS 7500XHV Power Supply User Manual


 
10
Selecting the Output Voltage via Terminal Mode
Terminal Mode is a menu driven interface that enables enhanced configuration of the uninterruptible power supply.
Connect the serial cable to the serial port on the back of the uninterruptible power supply.
When using the PowerChute
®
Network Shutdown utility:
1. Exit the PowerChute Business Edition agent and server using the following steps:
a. From the desktop, click Start=> Settings=> Control Panel=> Administrative Tools=> Services.
b. Select PCBE Server and PCBE Agent; then, right click the mouse and select Stop.
2. Open a terminal program, for example HyperTerminal.
From the desktop, click Start => Programs => Accessories => Communication =>HyperTerminal.
3. Double-click on the HyperTerminal icon.
a. Follow the prompts to choose a name and select an icon. Disregard the message,
must install a modem, if it is dis-
played. Click OK.
b. Select the COM port that is connected to your uninterruptible power supply. The port settings are:
# bits per second - 2400
# data - bits 8
# parity - none
# stop bit - 1
# flow control - none
c. Click Enter.
4. Once the blank terminal window is open, follow these steps to configure the output voltage:
a. Press Enter to initiate terminal mode. Press Enter multiple times, until the User Name prompt is displayed. Follow the
prompts. Type slowly, waiting until each character is displayed on the screen before typing the next character.
Network Management Card defaults:
User Name: apc
Password: apc
b. Press 1 and Enter to select Device Manager.
Select the number corresponding to the desired model and press Enter.
c. Press 3 and Enter to select Configuration.
d. Press 2 and Enter to select Line Transfer.
e. Press 3 and Enter to select Output Voltage.
Select the number corresponding to the desired voltage setting and press Enter.
f. Press 5 and Enter to Accept Changes.
g. Press Esc multiple times to return to the main menu.
h. Press 4 and Enter to log out.