IBM IBM UPS 7500XHV Power Supply User Manual


 
5
Positioning the Uninterruptible Power Supply
32–55 kg
(70–120 lb)
Attention: The uninterruptible power supply will remain heavy without the battery modules. Select a location
sturdy enough to handle the weight.
Do not operate the uninterruptible power supply in excessive dust or in temperature and humidity conditions outside the speci-
fied limits.
Make sure that the air vents on the front and rear of the uninterruptible power supply are not blocked.
Placement of the unit should correspond with the following graphical depiction.
Hardwiring the Uninterruptible Power Supply
Attention: Wiring must be performed by a qualified electrician.
1. Install a utility circuit breaker according to local electrical codes (see tables below) for input wiring.
200/208 V Applications
Input Connection Output Connection (Optional)
Single-Phase: Wire to L1, N, and .
Wire to L1A, N1, and
.
System Wiring Voltage Current
Full Load
(Nominal)
External
Circuit Breaker
(typical)
Wire Size
(typical)
Input 200/208 V 38 amps 50 amps / 2-pole 10 mm
2
UPS 7500XHV
Output 200/208 V 38 amps (as needed) 10 mm
2
Input 200/208 V 50 amps 63 or 70 amps / 2-
pole
16 mm
2
UPS 10000XHV
Output 200/208 V 50 amps (as needed) 16 mm
2
220/230/240 V Applications
Input Connection Output Connection (Optional)
Single-Phase: Wire to L1, N, and .
Three-Phase: Wire to L1, L2, L3, N, and .
Wire to L1A, N1, and
.
System Wiring Number
of
Phases
Voltage Current
Full Load
(Nominal)
External
Circuit Breaker
(typical)
Wire Size
(typical)
Input 1 220/230/240 V 38 amps 50 amps / 2-pole 10 mm
2
Input 3 380/400/415 V 14 amps/
phase when online,
38 amps on L1 in
bypass
50 amps/ 4-pole 10mm
2
UPS 7500XHV
Output 1 220/230/240 V 38 amps (as needed) 10 mm
2
Input 1 220/230/240 V 50 amps 63 amps / 2-pole 16 mm
2
Input 3 380/400/415 V 18 amps/ phase
when online, 50
amps on L1 in
bypass
63 amps/ 4-pole 16 mm
2
UPS 10000XHV
Output 1 220/230/240 V 50 amps (as needed) 16 mm
2