IBM IBM UPS 7500XHV Power Supply User Manual


 
15
NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE BUSINESS EDITION SOFTWARE, NETWORK
MANAGEMENT CARD, OR TERMINAL MODE. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
DESCRIPTION
Output Frequency Automatic
(50 ± 3 Hz or
60 ± 3 Hz)
Automatic,
50 ± 3 Hz,
50 ± 0.1 Hz,
60 ± 3 Hz,
60 ± 0.1 Hz
The user is able to set the allowable
uninterruptible power supply output
frequency. Whenever possible, the
output frequency tracks the input fre-
quency.
Number of Battery
Packs
1 Number of Con-
nected Battery Packs
(four battery modules
per pack)
The user can define the number of con-
nected battery packs for proper runtime
prediction.
Emergency Power Off (EPO) Option
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Note: Adhere to national and local electrical codes when wiring.
The switch should be connected in a normally open switch contact. External voltage is not required; the switch is powered by a
12 V internal power supply. A closed switch draws 2 mA of current.
The EPO switch is internally powered by the uninterruptible power supply for use with non-powered switch circuit breakers.
Note: The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal
block unless it can be confirmed that the circuit is Class 2 or SELV.
If the circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the uninterruptible power supply to the EPO switch:
CL2: Class 2 cable for general use
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft
CLEX: Limited use cable for use in dwellings and for use in raceways
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable)
For installation in other countries: Use a standard low-voltage cable according to local regulations
EPO
Switch