SSI
EPS1U Power Supply Design Guide, V1.1
8.4.2.2 MultiRecord Area
As defined by the IPMI FRU document. The following record types shall be used on this power supply:
• Power Supply Information (Record Type 0x00)
• DC Output (Record Type 0x01)
• No other record types are required for the power supply.
MultiRecord information shall be defined as follows:
Table 25: FRU Device MultiRecord Area
Field Name (PS Info) Field Information Definition
Overall Capacity (W) 350 {Low power versions would be 250 or 125}
Peak VA 400 {Low power versions would be 300 or 161}
Inrush current (A) 30
Inrush interval (ms) 5
Low end input voltage
range 1
90
High end input voltage
range 1
140
Low end input voltage
range 2
180
High end input voltage
range 2
264
A/C dropout tol. (ms) 20
Binary flags Set for: Not Hot Swap support, Auto-switch, and PFC
Peak Wattage Set for: 12 s, 400 W {Low power versions would be 300W or 161W}
Combined wattage Set for 5 V & 3.3 V combined wattage of 113 W {Low power versions would be 113W
or 80}
Predictive fail tach
support
Not supported, 00h value
Field Name (Output) Field Description: Six outputs are to be defined from #1 to #6, as follows: +3.3 V, +5
V, +12 V1, +12V2, -12 V, and +5 VSB.
Output Information Set for: Standby on +5 VSB, No Standby on all others.
All other output fields Format per IPMI specification, using parameters in the EPS1U specification.