Liebert 1500 Power Supply User Manual


 
16 Specifications
Figure 15 Front view of the (2) 400 A circuit breaker panel
The DC output connections can accommodate two 750 MCM cables back to back for each circuit
breaker. The required lugs must be for two 1/2” holes at 1-3/4” c-c.
Refer to
Table 21
for the maximum panel capacity.
The panel accepts up to:
two breakers (400 A) mid trip with or without the metering shunt option
one breaker (400 A) mid trip with the relay trip option (takes a 3 pole space)
Figure 16 Front view of the (1) 600-700 A circuit breaker panel
The DC output connections can accommodate four 750 MCM cables back to back. The lugs must
be for two 1/2” bolts at 1-3/4” c-c.
Refer to
Table 21
for the available circuit breakers and the maximum panel capacity.
Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panel
Nominal current CPC
400 A (no shunt) P0748316
400 A (with shunt) P0748317
2 x 400 A (no shunt) P0748318
2 x 400 A (with shunt) P0748319
400 A (with relay trip) P0748320
Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panel
Nominal current CPC
600 A (no shunt) P0875700
600 A (e/w shunt) P0875701
600 A (e/w relay trip) P0875702
900A MAX. PANEL CAPACITY
1
2
CIRCUIT BREAKER PANEL
NT6C12EF
FA
REL ( )
SER NO ( )
UNIT
AMPS
LOAD
400
400
1
2
(2) 400 A
900A MAX. PANEL CAPACITY
1
2
CIRCUIT BREAKER PANEL
NT6C12EG
FA
REL ( )
SER NO ( )
UNIT
AMPS
LOAD
600
1
(1) 600-700 A