Liebert 232 Network Card User Manual


 
© 1996-98 Liebert Corporation
15
Rev. (08-JULY-98)
LGM Module Driver
Parameter Page
Function Block Type: LGM (LGM Module Driver)
Name SiteGate-232 Line 1 LG 2 CM 1 FB 15 Flags —
ID ID14 Tele NB All Options Y Type 67 Ver 1
Power Up Delay 0 (sec) Demand Controller Address 0 ,0
Update Time 0:00 (mm:ss)
BACnet Device Parameters:
Use default device object name? Y Device Name =
Use default device object ID? Y Device ID = (device object, 0)
APDU Timeout ............. 3000 (milliseconds)
Number of APDU Retries ... 0
GFB performance tuning:
=======================
Time slice per GFB = 5000 milliseconds.
CMnet Parameters:
General:
Generate a “Dead Module” alarm after 10 minutes of no communications
with a control module.
Zero compression enabled? YES
Output character pacing? (reduces throughput by 50%) NO
Delay before sending all replies (20 msec minimum) = 20 msec.
Interpacket delay .............. (20 msec minimum) = 20 msec.
Alternate interpacket delay .... (40 msec minimum) = 40 msec.
CMnet Tuning Parameters: (Tech Support Only)
Time to wait for ‘?’ before attempting intrusive grab = 500 msec.
Maximum number of intrusive grab attempts per request = 3
Grab Silence Time = 600 msec.
Time to hold the token when the token wraps around = 1 seconds
Time to wait for each module to acknowledge the token = 500 msec.
Maximum online time per successful grab = 0:50 (mm:ss)
Maximum monitor time per monitor request = 5:00 (mm:ss)
Console Port #1 Parameters:
Modem installed on this console port = NO
Modem control parameters:
Modem Reset ATV0E0Q0S0=1S7=60
Dial Prefix ATDT
Phone Number
Use This Number? NO (NO = use number from SETGCM )
If not connected, and with no alarms pending delivery, reset modem
every 5:00 (mm:ss). Note: the minimum value for this is 5:00.
If connected, but no activity has been detected for 20:00 (mm:ss),
hang up and reset modem.
After dialing, wait 2:00 (mm:ss) for connection before hanging up.
After unsuccessful alarm delivery, wait 5:00 (mm:ss) before
trying again.
Escape (+++) guard time 1000 msec.
Post hangup delay 1000 msec.
Reset time (DTR low) 1000 msec.
Post DTR high delay 500 msec.
Post reset string delay 1000 msec.
Console Port #2 Parameters:
Modem installed on this console port = NO
Modem control parameters:
Modem Reset ATV0E0Q0S0=1S7=60
Dial Prefix ATDT
Phone Number
Use This Number? NO (NO = use number from SETGCM )