Appendix A - Site Planning Data 81
Table 4 Series 600T Multi-Module Systems, 500-750 kVA - 480 Volt Input
UPS
Rating
AC
Output
Voltage
Options
Rectifier
AC
Input
Current
Inverter
or
Bypass
AC Output
Current
Required
Battery
Discon-
nect
Rating
Maximum
Battery
Current
at End of
Discharge
Maximum
Heat Dis-
sipation
BTU/hr.
Dimen-
sions
Inches
Approx.
Weight
Lb.
Floor
Loading
Lb./
Sq.ft.
kVA kW
Input
Filter
Input
Iso
Xfmr Nom Max Nom Max Amps Amps
Full
Load (WxDxH)
(Un-
packed)
(Concen-
trated
Loading)
500 400 480 NO NO 602 753 601 752 1,000 1,079 87,150 72x39x79 5,710 293
500 400 480 YES NO 558 698 601 752 1,000 1,079 91,800 72x39x79 5,910 303
500 400 480 NO YES 612 765 601 752 1,000 1,079 110,700 96x39x79 8,710 335
500 400 480 YES YES 565 707 601 752 1,000 1,079 115,500 96x39x79 8,910 343
500 450 480 NO NO 677 847 601 752 1,200 1,214 98,050 72x39x79 5,730 294
500 450 480 YES NO 628 785 601 752 1,200 1,214 103,250 72x39x79 5,930 304
500 450 480 NO YES 688 861 601 752 1,200 1,214 124,550 96x39x79 9,030 347
500 450 480 YES YES 638 798 601 752 1,200 1,214 129,931 96x39x79 9,230 355
625 500 480 NO NO 749 936 752 936 1,400 1,349 99,300 108x39x79 7,405 285
625 500 480 YES NO 694 867 752 936 1,400 1,349 105,050 108x39x79 7,625 293
625 500 480 NO YES 757 946 752 936 1,400 1,349 118,650 120x39x79 10,485 323
625 500 480 YES YES 701 877 752 936 1,400 1,349 124,509 120x39x79 10,705 329
750 600 480 NO NO 898 1123 902 1128 1,600 1,619 119,200 108x39x79 8,005 308
750 600 480 YES NO 833 1041 902 1128 1,600 1,619 126,100 108x39x79 8,225 316
750 600 480 NO YES 908 1135 902 1128 1,600 1,619 142,350 120x39x79 11,485 353
750 600 480 YES YES 842 1052 902 1128 1,600 1,619 149,410 120x39x79 11,705 360
750 675 480 NO YES 1022 1277 902 1128 1,600 1,822 160,150 120x39x79 11,785 363
750 675 480 YES YES 947 1184 902 1128 1,600 1,822 168,100 120x39x79 12,005 369
Applicable
Notes:
—
13 — 1,4,5,7,8,
9,11,12
2,3,5,7,8,
9,11,12
6 6,8,9,
11,12
— 14 14 —
For explanation of notes, see referenced numbers in 12.1 - Notes