21
SPECIFICATIONS
MODEL NUMBER GXT1800RT-208 GXT2700RT-208 GXT96VBATT
MODEL RATING VA/W 1800 / 1290 2700 / 1890
DIMENSIONS: in (mm)
Unit
W x D x H
7.0 x 19.3 x 16. 9
(177 x 522 x 430)
7.0 x 19.3 x 16. 9
(177 x 522 x 430)
7.0 x 19.3 x 16. 9
(177 x 522 x 430)
Shipping
W x D x H
13.38 x 26.0 x 22.25
(340 x 660 x 565)
13.38 x 26.0 x 22.25
(340 x 660 x 565)
13.38 x 26.0 x 22.25
(340 x 660 x 565)
WEIGHT: lbs (kg)
Unit 80.9 (36.8) 85.9 (39.0) 71.6 (32.5)
Shipping 88.0 (40.0) 93.0 (42.3) 78.7 (35.8)
INPUT AC PARAMETERS
Voltage Range (typical) 208 VAC nominal; variable based upon output
load
100% - 90% Loading 191 VAC to 275 VAC
90% - 70% Loading 164 VAC to 275 VAC
70% - 30% Loading 144 VAC to 275VAC
30% - 0% Loading 124 VAC to 275VAC
Frequency 48 – 52 Hz or 58 – 62 Hz; auto sensing
Input Power Cord 6 ft. attached, w/
NEMA L6-15 plug
6 ft. attached, w/ NEMA
L6-20 plug N/A
OUTPUT AC PARAMETERS
Output Receptacles (2) NEMA L6-15R (2) NEMA L6-15R,
(1) NEMA L6-20R N/A
Voltage 208/220/230/240 (switch selectable) VAC; ±3%
Frequency 50 Hz or 60Hz
Waveform Sinewave
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with
transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating 8 x 12V x 7 or 7.2 AH 8 x 12V x 7 or 7.2 AH 8 x 12V x 7 or 7.2
AH
Batt. Mfg./ Part # CSB GP1270F2 or Panasonic LC-R127R2CH1
Back-up Time See Typical Battery Discharge Curves
Recharge Time 5 Hours to 95% capacity after full discharge into
100% load
Adds 5 hours per
additional battery
cabinet
ENVIROMENTAL
Operating Temperature +32° F to +104° F (0° C to +40° C)
Storage Temperature +5° F to +122 °F (-15° C to +50° C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to10,000 ft. (3000 m) at 40° C without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise <45 dBA, at 1 meter
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Immunity
IEEE 587 Category A