Liebert Series 610 Power Supply User Manual


 
Operating Instructions
37
Figure 20 One system in bypass to Continuous Tie operation (Option 1)
Figure 21 One system in bypass to Continuous Tie operation (Option 2)
M
1
M
1
SS
1
SS
2
M
2
M
2
System 1 System 2
Load 1 Load 2
Tie
M
1
M
1
SS
1
SS
2
M
2
M
2
System 1 System 2
Load 1 Load 2
Tie
FROM:
One System in Bypass Mode
Tie Open
Restart the bypassed system, then use the procedures in Tying the UPS Systems - Continuous
Parallel Operations (in Section 4.2.11) or see Figure 21.
LEGEND: M
x
= Module
SS
x
= Static Bypass Switch
M
1
M
1
SS
1
SS
2
M
2
M
2
System 1 System 2
Load 1 Load 2
Tie
Tie Closed
TO:
Continuous Tied Systems
TO:
Restart Bypassed System
Tie Open
Partial
or full
capacity
M
1
M
1
SS
1
SS
2
M
2
M
2
System 1 System 2
Load 1 Load 2
Tie
FROM:
One System in Bypass Mode
Tie Open
Combined loads on one system—See 4.2.4 - Isolating a UPS System for Maintenance - Combined
Loads Operation; restart bypass system. Then use Continuous Tie procedures—Tying the UPS
Systems - Continuous Parallel Operations in Section 4.2.11.
Restart one system, then refer to Figure 20. Or restart both systems, then refer to Figure 15.
LEGEND: M
x
= Module
SS
x
= Static Bypass Switch
M
1
M
1
SS
1
SS
2
M
2
M
2
System 1 System 2
Load 1 Load 2
Tie
Tie Closed
TO:
Continuous Tied Systems
M
1
M
1
SS
1
SS
2
M
2
M
2
System 1 System 2
Load 1 Load 2
Tie
Tie Closed
TO:
Combined Loads Operation
Momentary Tie
for transfer of
Load 2 to
System 1
Partial or
full capacity