Liebert VM18000 Power Supply User Manual


 
30
External Battery Cabinets
WARNING: Remove UPS battery fuses and open the Battery
Cabinet circuit breaker before removing the battery cable
connectors cover plate. These connectors contain lethal
voltages when the circuit to the battery is complete.
Standard External Battery Cabinets
Matching stand-alone cabinet(s) can be provided with
additional string(s) of low-maintenance batteries for additional
back-up time in conjunction with the UPS internal battery. Each
cabinet includes a fuse and a circuit breaker disconnect. The
UPS-to-battery cabinet wiring allows for cabinet location directly
adjacent to the UPS module. See Figures below and on the
following page. See Battery Time Curves in Appendix.
Battery
CB (35A)
External
Connectors
Battery
Fuse (30A)
Rear View
Top View
VBD061
3.5-6 kVA
Battery
Fuse
(30A)
Battery
CB (30A)
External
Connectors
Rear
View
VBS061 / VBS062
3.5-6 kVA
Battery
CB (70A)
External
Connectors
Battery
Fuse (70A)
VBD121
8 - 12 kVA
Rear View
Top View
Battery
CB (30A)
Battery
Fuse
(30A)
External
Connectors
Rear View Top View
VBS122
8-12 kVA
VBD 181
15-18 kVA
Battery
CB (100A)
Access
Plate for
Power
Cable
Entry
Rear View
Top View
(Cover Removed)
Battery
Fuse (100A)
Power Terminal
Block Wire
Range:
(4) #14 - #4 per
Connection
Two Ground
Lugs Wire
Range:
(1) #14 - #1/0
Each
Battery
CB (100A)