module config
NO configuration required
Name Description Values Meaning
1A1A/bb/CC
(1)
Module 1 configuration
id
Identity of module installed
nonE
Module not fitted
rELy
Relay output
dC.OP
Non-isolated DC output
(1) If a dual-, or triple-, channel
LoG
Logic/ output
module is installed then the list
LoG.i
Logic input
headers 1b and 1C also appear
SSr
Triac output
dc.rE
DC retransmission
(isolated)
dc.OP
Isolated DC output
For ‘idid’ = ‘rELy’, ‘LoG’, or ‘SSr’ use this parameter table:
Func
Function
nonE
Function disabled
dIG
Digital output function
(Only Channels 1A and 1C can be HEAt
Heating output
Heating, or Cooling)
COOL
Cooling output
up
Open motorised valve
dwn
Close motorised valve
(Only if id’ = ‘LoG’) SSr.1
mode 1 heating
(Only if id’ = ‘LoG’) SSr.2
mode 2 heating
VAL.L
% PID demand signal
giving minimum output
Out.L
VAL.H
% PID demand signal
giving maximum output
Out.H
Out.L
Minimum average power
Out.H
Maximum average power
SEnS
Sense of output
(Only ifFunc’ = dIG’)
nor
Normal (output energises
when TRUE, e.g
program events)
inv
Inverted (output de-
energises when TRUE,
e.g. alarms)
Notes:
1. When SEnS appears, then further parameters are available.
These are identical to those in the AA ConF list on Page 6-12.
VAL.L
100%0%
VAL.H
Displayed Value
Retransmitted
Output