2.3. TECHNICAL SPECIFICATIONS
Standards
Construction and safety : IEC-60439-1
Conception : IEC-60289, IEC-60727
IP rating
Unprotected : IP00
Protected : IP21
Electrical specifications
Frequency : 50 / 60Hz
Nominal voltage between phases : 400V +15% / -10%
Reduction ratio
I
I
Neutralupstream
Neutraldownstream
1:10
Ratio
I
I
Neutral
Phase
: 1.8
Inrush current : I
nominal
Overload capacity : 10% - 1 hour
25% - 10 minutes
50% - 2 minutes
Insulation class : 1.1 kV
Dielectric strength : 3 kV
Thermal class of insulation: H
Environmental conditions
Maximum ambient temperature : 50°C
Maximum altitude : 1000m
Maximum relative humidity : 90% without condensation
Please contact your MGE UPS SYSTEMS correspondent for different operating conditions.