MGE UPS Systems 6000 Power Supply User Manual


 
MGE
TM
Galaxy
TM
6000 : Specification guide
Parallel UPS, three-phase, 250 to 3000 kVA*
* Power rating for an N+1 redundant configuration
APC By Schneider Electric Edition - 03/2009 Spec. E - 18
Appendix. Comparison table
Type of UPS
Total rated power (kVA) at PF 0.8
kVA
Manufacturer
Range of products
Operating mode (IEC 62040-2) double conversion
yes no
Parallel connection 4 modules without interrupting
operation
kVA max. yes
no
Rectifiers
Three-phase input voltage at Pn
380 or 400 or 415 V ± 15 % yes no
Rated active power
constant for loads with cos ϕ 0.8 lagging
to cos ϕ 0.9 leading
yes
no
Frequency 50 or 60 Hz ± 10 % yes no
Sinusoidal input current
THDI u
p
stream
4 % with THM filter
yes no
Input power factor PF > 0.94 yes no
No inrush or start-up current
yes no
Rapid battery charger
Backup time 10 minutes in t 11 hours,
4 hours in t 24 hours
yes no
Voltage regulation ± 1 %
yes no
Independent regulation/monitoring systems
yes
no
Battery
Type
standard
sealed lead acid in a cabinet
yes no
other
yes no
Service life years
yes no
Backup time minutes
yes no
Battery management and protection
Temperature correction
yes no
Measurement of actual backup time,
depending on:
load, temperature, age yes
no
Cold start on battery power
yes no
Protection against deep discharge
with circuit-breaker opening yes no
Charge-current limiting 0.05 C10 to 0.1 C10 (depending on the
battery)
yes
no
Self-tests
yes no
Calculation of real backup time
yes no
Block by block monitoring
yes no