MGE UPS Systems 6000 Power Supply User Manual


 
MGE
TM
Galaxy
TM
6000 : Specification guide
Parallel UPS, three-phase, 250 to 3000 kVA*
* Power rating for an N+1 redundant configuration
APC By Schneider Electric Edition - 03/2009 Spec. E - 19
Inverter
Three-phase output voltage with neutral
Volts yes no
adjustable ± 3 % yes no
Steady-state conditions ± 1% yes no
Voltage transients ± 3% (load from 0 to 100 or 100 to 0 %) yes no
Output voltage distortion at Pn
THDU ph-N < 4% for linear loads yes no
THDU ph-N < 4% for non-linear loads yes no
Output frequency
Hz yes no
Variation in output frequency
± 0.5 Hz yes no
adjustable ± 0.25 Hz to 2 Hz
yes non
Frequency synchronisation with an external
source
± 8 % of rated frequency
yes
no
Overload capacity 125% In for 10 minutes
yes no
165% In for 1 minute
yes no
Current limiting 233% In for 150 milliseconds
yes no
Crest factor up to 3:1
yes no
Static bypass
Static bypass
yes no
Short-circuit withstand of static bypass depending on power
yes no
Maintenance bypass
yes no
Efficiency
Normal mode
> 95% at Pn, > 92 % at Pn/2
yes no
User interface
Graphic display 15 languages selection of operating language
yes no
personalisation menu with password
yes no
display measurements, status, events, graphs
yes no
event log Time-stamping 2000 events
yes no
Controls ON, OFF, EPO terminal block
yes no
Status indications with mimic panel Audio alarm, LEDs
yes no