MGE UPS Systems 66103 Computer Hardware User Manual


 
ENERGIZE YOUR ENTERPRISE
Network Management Card
– User Manual 34003991EN/DA Page 93/120
7.4.2 Data for Pulsar M 2200 / 3000
7.4.2.1 Status table
Status description Status to 0 Status to 1 Word (hex) Bit
Load protected no yes 40 0
UPS coupled no yes 40 1
Unit general alarm no yes 40 2
UPS in backup no yes 40 4
Battery low warning no yes 40 5
Low battery no yes 40 6
Operation on static switch no yes 40 7
Communication fault absent present 40 9
UPS overload no yes 40 A
Emergency stop absent present 40 B
Battery to be checked no yes 40 D
Device ventilation fault no yes 40 E
Manual bypass switch (Q3BP) open closed 41 6
Battery present absent present 42 0
Mains 1 voltage out of tolerance no yes 44 8
Mains 1 frequency out of tolerance no yes 44 B
Redundancy lost no yes 45 7
Maintenance position no yes 46 1
Mains 2 overload no yes 46 5
Output on bypass no yes 46 7
Mains 2 frequency out of tolerance no yes 46 9
Mains 2 voltage out of tolerance no yes 46 A
Phase M2 out of tolerance no yes 46 B
Charger general fault no yes 49 0
Battery charge no yes 49 1 & 3
Converter fault no yes 4A 1
Inverter major fault no yes 4C 1