MGE UPS Systems EX30 Power Supply User Manual


 
30
Pulsar EX: 51032306XT/BB MGE UPS SYSTEMS
AC power
(single-phase +
earth)
30
29
12
26
24
25
output
to load
XB2
XB1
NNPh Ph
6
7
Pulsar EX with the "manual
bypass" module ("Install"
version)
c ensure that the "automatic bypass"
module 21 is properly installed;
c take the "manual bypass" module 31 ;
c plug the rear connectors into connectors
4 and 6 of Pulsar EX (see figure 5);
c tighten the module using the 2 screws 24 ;
c plug the connecting cable 26 into the
connector 12 of Pulsar EX;
c connect the loads having to be supplied
by Pulsar EX:
v open the cover protecting the terminal
blocks, pass the cable in the left cable-
clamp and connect the 3 wires (phase,
neutral and ground) to the output terminal
block 29 (XB2).
c connect Pulsar EX to the AC supply;
v pass the cable in the right cable-clamp
and connect the 3 wires (phase, neutral and
ground) to the input terminal block 30
(XB1) and put back the protective cover;
c do not connect the supply cable to the AC
outlet if the battery extension module option
has to be installed, else directly consult the
"operation" section.
Figure 5