MGE UPS Systems EX30 Power Supply User Manual


 
Pulsar EX: 51032306XT/BB 27
MGE UPS SYSTEMS
11
5432
1
9876
0V
RD TD
SNMP communication
The communication port 13 located on the
back of Pulsar EX, supplies SNMP-
compliant data on an RJ45 connector.
The label on the top of the connector 13
gives the device’s MAC address.
13
5432
1
876
TD+
TD-
RD-
RD+
0080C8ABAA01
communication
Relay breaking capacity:
Vmax = 30V
Imax = 100mA
n.o. : normalement open,
n.c. : normalement closed
10
n.o.
n.c.
n.o. n.o.n.o.
5432
1
9
876
common
You may use EX Driver software 18 to
customise Pulsar EX to suit your operating
conditions (EX Tuner), supervise your UPS
and protect your system (UPS Manager 3.1).
To install EX Driver, connect one end of the
supplied communications cable to the serial
port (declared as COM1 to COM4) of your
computer and the other end to the port 11
on Pulsar EX. EX Tuner requires Windows
3.1 or Windows 95 and may be used to set
up the serial port on the computer. To install
the software, insert the diskette and run
A:\install. Follow the instructions that appear
on the screen. Two software utilities will be
installed:
c EX Tuner, which may be used to
customise Pulsar EX;
c UPS Manager 3.1, for supervising and
protecting your system.
RS232/ASCII communication
The "U-Talk" communications port 11
(RS232 serial link), located on the back of
Pulsar EX, supplies information supported
by the exclusive MGE UPS SYSTEMS
communications protocol.
Data supplied by this protocol can be
analysed by Solution-Pac™ software.
status information
The "Basic" communications port 10 ,
located on the back of Pulsar EX, supplies
information on the status of Pulsar EX. It
consists of a SUB-D 9 female connector with
the following pin-outs:
1- earth,
4- operation on AC power,
5- common,
6 - operation on "automatic bypass",
7- low-battery shutdown warning,
8- operation on UPS,
9- operation on battery.
c your MAC address is of the type:
0080C8 ZZ XX YY;
c your IP default address is:
168.xx.yy (where xx and yy are the decimal
values of XX and YY).
In the above example, the address IP
168.8.170.1 corresponds to the MAC
address 0080C8 AB AA 01.
Please consult the user manual in the
directory emb/ex/snmp/ex-i2c/release 3xx of
the Solution-Pac™ CD-ROM to benefit from
the administration potential of your
Pulsar EX (SNMP version).
Contact your retailer for further details.