MGE UPS Systems EX30 Power Supply User Manual


 
Pulsar EX : 51032306XT/BB MGE UPS SYSTEMS
38
reconnecting Pulsar EX
Operating mode:
c take the "manual bypass" module 25 or
31 and connect it behind Pulsar EX;
c screw on this module using the 2 screws
24 ;
c plug the cable 26 into the connector 12
on Pulsar EX;
c close the battery circuit-breaker 7 on
Pulsar EX (as well as the circuit-breakers
32 on the Pulsar EXB battery extension
modules if fitted): "l" position;
c with the "manual bypass" switch 28 set
to "BY-PASS", depress the button 3 ;
c check after 15 seconds that Pulsar EX
has started properly and that the following
indications are obtained:
c if the indicator lights are in a status other
than that indicated, do not switch the "manual
bypass" and contact our after-sales service;
c switch the "manual bypass" 28 from the
"BY-PASS" position to the intermediate
position (see figure 10).
The following indications are obtained:
1a
to
1c
off
intermittent beeps
!
-
+
%
-
+
1f
flashing
1e
off/power on
1d
flashing/operation on
"manual bypass"
"manual bypass" switch
28
BY-PASSNORMAL
"NORMAL" position
BY-PASSNORMAL
intermediate position
BY-PASSNORMAL
"BY-PASS" position
1a
to
1d
intermittent beeps
!
-
+
%
-
+
n/a
1f
flashing/load in
"automatic
bypass"
1e
off/power on
c switch the "manual bypass"
28
from the
intermediate position to the "NORMAL"
position: operation is now normal and the
following indications are obtained:
!
-
+
%
-
+
1a
to
1d
indicate battery state
1f
on/load energized
silence
1e
off/power on
flashing/power off
Figure 10