MGE UPS Systems EX-7 Power Supply User Manual


 
Installation and User Manual
1.1 System Electrical Characteristics
Table 1-3: UPS Characteristics System Ratings.
Table 1-4: Transformer Module Characteristics Ratings.
CAUTION Power Module is factory configured at 208Vac, 60 Hz input and output.
Without transformer, Input and Output of the UPS must always be
the same.
On 11KVA, 10% de-rating for 200/208VAC. Isolated 120/208/240VAC are
available with EX RT Transformer Module.
Introduction 1 — 386-86000-00 B00
UPS Characteristics
MAIN 1 (Normal AC Source) default
Power
Rating
Input
Voltage
(VAC)
Input Current (A)
Input
Breaker
(A)
Output
Voltage
(VAC)
Output
Current
(A)
Inrush
Current
Min Max Online Bypass
5 kVA
208
18 32 21.6 19 40
208
19.25
200A/1ms7 kVA 25 45 30.3 26.65 50 23.5
11 kVA 38 64 44 42 70 47.5
Transformer Module Characteristics
Input Voltage (VAC) 208/240
Output Voltage (VAC) 120/120 208 240
Max. Output Current (A) 33.3/33.3 52 45