MGE UPS Systems EX-7 Power Supply User Manual


 
Table 3-3: ON/OFF Features.
Display Factory setting Options Comments
Cold start Disabled Enabled Start on battery.
Forced reboot Enabled Disabled UPS restarts automatically
when normal AC source
is restored.
Automatic restart Enabled Disabled UPS restarts automatically
when normal AC source
is restored.
Sleep mode Disabled Enabled Automatic shutdown on battery
if output load level <10%
Remote Command Enabled Disabled Enables shutdown or restart
orders from software.
Table 3-4: Battery Features.
Display Factory setting Options Comments
Battery test Every week No test/daily/monthly
Pre-Alarm 20% 0 to 100% Low battery signal;1% increment
Runtime choice UPS reads # and type From 50 to 400 Ah Requires CLA Module if using
of Battery Modules options (see section 1.5.8)
connected.
Battery deep discharge Enabled Disabled If disabled, loss of
protection MGE UPS SYSTEMS, INC.
warranty.
EX 5/7/11RT Systems
Operation3 — 4 86-86000-00 B00