MGE UPS Systems EPS 8000 Power Supply User Manual


 
Q5N UPS OUTPUT ISOL.
SWITCH OPEN !
This message indicates that the optional UPS isolation circuit breaker Q5N is open. The load is not supplied unless
the maintenance bypass circuit breaker Q3BP is closed.
Q3BP MAINT. BYPASS
SWITCH CLOSED !
This message indicates that the optional maintenance bypass circuit breaker Q3BP is closed. The system is set to
maintenance bypass, and the load is supplied by the bypass AC input source (mains 2).
STATIC SWITCH O.L.
EMERGENCY OFF !
This message indicates that the static switch has shut down following an overload condition, disconnecting the load.
DISPLAY NUMBER 1
UNAVAILABLE
This message indicates that the alphanumeric display is not operating properly. The status of the UPS is still
correctly indicated by the LEDs of the visible panel and the hidden panel, see section 1.5 Single Module Indicators
and Controls.
HARMONIC FILTER
FUSE FAILED
This message indicates that the fuse(s) protecting the input harmonic filter has opened and that service is required.
The status of the UPS is still correctly indicated by the LEDs of the visible panel. Refer to section 1.5 Single Module
Indicators and Controls for front and hidden panel indicators and controls.
Operation
EPS 8000 UPS Single Module
page 2 —12