MGE UPS Systems 2200RT Power Supply User Manual


 
Page 18 - 3400753300/AE
16
Press button 16 (return to the OFF position).
The connected equipment is no longer supplied with power.
3.5 UPS shutdown
"Bypass" tab
"Output" tab
Options
Disabled (click to remove check)
Enabled (click to add check)
Default setting
Enabled
Disabled
Personalization function
Transfer to bypass if overload
Transfer to bypass following a fault, whatever the
conditions on the AC-power source
Options
100 V - 127 V
Converter
50 Hz
F ± 1% to ± 10%, in 1% steps
0 to 110%, in 10% steps
Enabled (click to add check)
Default setting
120 V
Autoselect
F = 60 Hz
F ± 5%
110%
Disabled
Personalization function
Rated UPS voltage
Frequency working mode
Rated UPS frequency
UPS tolerance for AC-power
source frequency
Overload alarm threshold
UPS restart following short-circuit
3. Operation
test
1
2
BYPASS