2. Installation
2.5 Connection with a FlexPDU (Power Distribution Unit) module (optional)
2.6 Connection with a HotSwap MBP module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads
(HotSwap function).
1 - Evolution S 2500 / S 3000: connect the
UPS input socket (10) to the AC-power
source using the cable (31) supplied.
Evolution S 1250 / S 1750 / 2000: use the
power cable of the protected equipment.
2 - Evolution S 2500 / S 3000: connect the
input socket on the FlexPDU module (48) to
the UPS outlet (7) using the cable (41)
supplied.
Evolution S 1250 / S 1750 / 2000: connect
the input socket on the FlexPDU module
(48) to one of the outlets (9).
The cable and the connectors are marked in
red.
3 - Connect the equipment to the outlets (45),
(46) and (47) on the FlexPDU module. These
outlets differ, depending on the version of the
FlexPDU module.
4 - Fit the connection securing system that
prevents the plugs from being pulled out
accidentally.
1 - Connect the input socket (56) on the
HotSwap MBP module to the AC-power
source using the cable (31) supplied.
2 - Connect the UPS input socket (10) to the
"UPS Input" (55) on the HotSwap MBP
module, using the cable (44) supplied. These
cables and the connectors are marked blue.
3 - Evolution S 2500 / S 3000: connect the
UPS outlet (7) to the "UPS Output" (54) on
the HotSwap MBP module, using the cable
(44) supplied.
Evolution S 1250 / S 1750 / 2000: connect
one of the UPS outlets (9) to the "UPS
Output" (54) on the HotSwap MBP module.
These cables and the connectors are marked
in red.
4 - Connect the equipment to the outlets (49)
and (50) on the HotSwap MBP module.
These outlets differ, depending on the
version of the HotSwap MBP module.
Caution. Do not use UPS outlets (8) and (9)
to supply equipment because use of
switch (53) on the HotSwap MBP module
would cut supply to the equipment.
7
8
9 10
48474645
FlexPDU
41
31
Evolution S 2500 / S 3000
7
8
9 10
By-pass
Normal
UPS ON -
OK to switch
BY PASS SWITCH
56
5549
HotSwap MBP
50
545351 52
44
31
Evolution S 2500 / S 3000