MGE UPS Systems S 1250 RT 2U, S 1750 RT 2U, 2000 RT 2U, S 2500 RT 2U, S 3000 RT 2U, S 3000 RT 3U, S EXB 1250/1750 RT 2U, S EXB 2500/3000 RT 2U, S EXB 2500/3000 RT 3U Power Supply User Manual


 
34008236EN/AA - Page 20
6. Appendices
6.1 Technical specifications
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
(3) Adjustable to 200 V (10% derating of output power) / 208 V / 220 V / 230 V / 240 V.
(4) Battery Evolution S EXB 1250/1750: 2 strings, each 4 x 12 V / 9 Ah.
(5) Battery Evolution S EXB 2500/3000: 2 strings, each 6 x 12 V / 9 Ah.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16A, 250V which is IEC/EN
60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20A, 250V.
This product is designed for IT power distribution system.
Evolution S
1250
Evolution S
1750
Evolution
2000
Evolution S
2500
Evolution S
3000
Output power 1250VA/1150W 1750VA/1600W 2000VA/1600W 2500VA/2250W 3000VA/2700W
AC input power
Rated input voltage
Input-voltage range
Input-frequency range
Single phase 220~240 V
160 V to 294 V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
Voltage
Frequency
230 V (+6/-10%)
(3)
50/60 Hz ±0.1%
Battery (sealed lead acid,
maintenance free)
Standard
Additional modules possible
(up to 4 EXB)
4 x 12 V
7.2 Ah
4 x 12 V - 9 Ah 6 x 12 V
7.2 Ah
6 x 12 V
9 Ah
Evolution S EXB 1250/1750
(4)
No Evolution EXB S 2500/3000
(5)
Environment
Operating temperature
range
Storage temperature range
Relative humidity
Noise level
0 to 40°C
-25°C to 40°C
20 to 90% (without condensation)
< 45 dBA < 50 dBA
Filter
Transformer
(AVR)
Charger
Inverter
Battery