MGE UPS Systems S 1250 RT 2U, S 1750 RT 2U, 2000 RT 2U, S 2500 RT 2U, S 3000 RT 2U, S 3000 RT 3U, S EXB 1250/1750 RT 2U, S EXB 2500/3000 RT 2U, S EXB 2500/3000 RT 3U Power Supply User Manual


 
34008236EN/AA - Page 16
4. Personalisation using external software
Main-output personalisation
Voltage-threshold personalisation
(1) Low threshold for transfer to battery is 150 V.
UPS-sensitivity personalisation
UPS ON/OFF personalisation
Battery personalisation
Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal
Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal Solution-Pac software).
Function Factory setting Other available settings
Output voltage
on battery power 230 Volts AC 200/208/220/240 Volts AC
Overload alarm threshold 105% 30/50/70%
Function Factory setting Other available settings
High threshold for transfer to battery 294 Volts AC 271 to 294 Volts AC
Low threshold for transfer to battery 160 Volts AC 160 to 180 Volts AC
Fader activation threshold 265 Volts AC 244 to 265 Volts AC
Booster activation threshold 184 Volts AC 184 to 207 Volts AC
Maximum input-voltage range Disabled Enabled
(1)
Function Factory setting Other available settings
UPS-sensitivity level Normal High or low
Function Factory setting Other available settings
Automatic start Enabled Disabled
Cold start Enabled Disabled
Forced shutdown Enabled Disabled
Energy-savings mode Disabled Enabled
UPS ON/OFF controlled by software Enabled Disabled
Battery level before restart 0% 0 to 100%
Function Factory setting Other available settings
Battery-test intervals Weekly No test / daily test / monthly test
Low-battery warning 20% 0 to 100%
Battery protection against deep discharge Enabled Disabled
Audio alarm Enabled Disabled
Additional battery module (Evolution S models only) Automatic detection of number
of battery modules
For specific batteries, from 25
to 81 Ah