Default: 120VAC (208VAC), User selectable: 127VAC (240VAC)
750VA
600W
1500VA
1200W
1000VA
800W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Sine Wave
Frequency
50/60Hz, +/-0.1Hz (unless synchronized to utility)
Nominal Voltage
Maximum Power Capacity
2-6 ms Typical
>93% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0 - 165VAC (0 - 300VAC)
80 - 164VAC (150 - 271VAC)
120VAC: 105 - 134VAC (208VAC: 189 - 236VAC)
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
E1500RM2U
E1500RMT2U
E1000RM2U
E750RM2U
Model Number
SYSTEM SPECIFICATIONS
Voltage Range
Topology
Line-Interactive, Sine Wave
OUTPUT NON-BATTERY OPERATION
INPUT
Number of Phase Single (1∅ 2W +G)
Nominal Voltage 120VAC (208VAC)
Low Voltage Transfer Point
80V (150V) resets to Utility Power at 85V (157V) or higher
High Voltage Transfer Point
164V (271V) resets to Utility Power at 159V (264V) or lower
Voltage Regulation
120VAC: -12.5% - +11.7% (208VAC: -9.1% - +13.5%)
Frequency Range 60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BATTERY OPERATION
Voltage Regulation Nominal +/-5% (until Low Battery Warning)
Voltage T.H.D.
<5% (Linear Load)
+/-10% @ 100% Load change in 30 ms
Dynamic Response
Slew Rate
<1Hz / second
Overload Capacity
110% for 20-seconds
125% for 10-seconds
150% Shutdown Immediately
E2000RM2U
E3000RM2U
E3000RMT2U
2000VA
1760W
3000VA
2560W