Moxa Technologies 5110 Series Network Card User Manual


 
NPort 5110 Series User’s Manual Web Console Configuration
5-17
( 10 (bits) / 1200 (bits/s) ) * 1000 (ms/s) = 8.3 ms.
Therefore, you should set Force transmit timeout to be larger than 8.3 ms, so in this case, it must
be greater than or equal to 10 ms.
If the user wants to send a series of characters in the same packet, the serial device attached to
NPort 5110 should send that series of characters during a time interval less than the Force transmit
timeout for NPort 5110, and the total length of data must be less than or equal to NPort 5110’s
internal buffer size. The serial communication buffer size for NPort 5110 is 1 KB per port.
Destination IP address 1
Setting Factory Default Necessity
IP address or Domain Name
(E.g., 192.168.1.1)
None Required
Allows NPort 5110 to connect actively to the remote host whose IP address is set by this
parameter.
Destination IP address 2/3/4
Setting Factory Default Necessity
IP address or Domain Name
(E.g., 192.168.1.1)
None Required
Allows NPort 5110 to connect actively to the remote host whose IP address is set by this
parameter.
ATTENTION
Up to 4 connections can be established between NPort 5110 and hosts. The connection speed or
throughput may be low if one of the four connections is slow, since the 1 slow connection will
slow down the other 3 connections.
ATTENTION
The “Destination IP address” parameter can use both IP address and Domain Name. For some
applications, the user may need to send the data actively to the remote destination domain name
TCP connect on
Setting Factory Default Necessity
Start up,
Any character
Start up Required
Start up: Attempts to establish a TCP connection as soon as the NPort 5110 is powered on.
Any Character: Attempts to establish a TCP connection as soon as the NPort 5110 starts receiving
serial data.