— 5 —
Wall Mounting (Optional)
For some applications, you will find it convenient to mount MOXA
EDS-510A on the wall, as shown in the following illustrations:
STEP 1—Remove the
aluminum DIN-Rail
attachment plate from the rear
panel of the EDS-510A, and
then attach the wall mount
plates, as shown in the figure
at the right.
Ö
STEP 2—Mounting the EDS-510A on the wall requires 4
screws. Use the EDS-510A, with wall mount plates attached, as a
guide to mark the correct locations of the 4 screws. The heads of
the screws should be less than 6.0 mm in diameter, and the shafts
should be less than 3.5 mm in diameter, as shown in the figure on
at right.
6.0 mm
3.5 mm
NOTE
Before tightening the screws into the wall, make sure the screw
head and shank size are suitable by inserting the screw through
one of the keyhole-shaped apertures of the Wall Mounting Plates.
Do not screw the screws in all the
way—leave about 2 mm to allow
room for sliding the wall mount
panel between the wall and the
screws.
STEP 3—Once the screws are fixed
to the wall, insert the four screw
heads through the wide parts of the
keyhole-shaped apertures, and then
slide the EDS-510A downwards, as
indicated in the figure at the right.
Tighten the four screws for more
stability.
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra-Low Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with the
Safety Extra-Low Voltages (SELV) in compliance with IEC950/
EN60950/ VDE0805.