Chapter 4 Signal Connections
6023E/6024E/6025E User Manual 4-12 ni.com
Figure 4-4. Summary of Analog Input Connections
Input
Differential
(DIFF)
Single-Ended —
Ground
Referenced
(RSE)
Single-Ended —
Nonreferenced
(NRSE)
Floating Signal Source
(Not Connected to Building Ground)
Grounded Signal Source
Examples
• Ungrounded Thermocouples
• Signal conditioning with isolated outputs
• Battery devices
Examples
• Plug-in instruments with
nonisolated outputs
+
-
+
-
V1
ACH(+)
+
-
+
-
V1
ACH(+)
ACH (-)
See text for information on bias resistors.
See text for information on bias resistors.
R
Signal Source Type
ACH (-)
AIGND
+
-
+
-
V1
ACH
AIGND
+
-
+
-
NOT RECOMMENDED
ACH
+Vg -
V1
Ground-loop losses, Vg, are added to
measured signal
+
-
+
-
V1
ACH
AISENSE
R
AIGND
+
-
+
-
V1
ACH
AISENSE
AIGND
AIGND