National Instruments FP-DO-403 Network Router User Manual


 
FIELDPOINT
OPERATING INSTRUCTIONS
AND SPECIFICATIONS
FP-DO-403 and cFP-DO-403
16-Channel, 5 to 30 V Sinking Digital Output Module
These operating instructions describe how to install and use the
National Instruments FP-DO-403 and cFP-DO-403 digital output
modules, referred to inclusively as the [c]FP-DO-403. For
information about configuring and accessing the [c]FP-DO-403
over a network, refer to the user manual for the FieldPoint network
module you are using.
Features
The [c]FP-DO-403 is a FieldPoint digital output module with the
following features:
16 sinking digital output channels
Outputs that sink 2 A per channel, 16 A
2
per module
Compatible with voltages from 5 to 30 VDC
250 V
rms
CAT II continuous channel-to-ground isolation,
verified by 2,300 V
rms
, 5 s dielectric withstand test
–40 to 70 °C operation
ON/OFF LED indicators
Hot swappable
Installing the FP-DO-403
The FP-DO-403 mounts on a FieldPoint terminal base (FP-TB-x),
which provides operating power to the module. Installing the
FP-DO-403 onto a powered terminal base does not disrupt the
operation of the bank.
To install the FP-DO-403, refer to Figure 1 and complete the
following steps:
1. Slide the terminal base key to either position X, used for any
module, or position 6, used for the FP-DO-403 module.