National Instruments FP-DO-403 Network Router User Manual


 
[c]FP-DO-403 10 ni.com
Caution For Zone 2 applications, install a protection
device across the external power supply and the COM
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The [c]FP-DO-403 has been evaluated as EEx nC IIC T4
equipment under DEMKO Certificate No. 03 ATEX 0251502X.
Each module is marked II 3G and is suitable for use in Zone 2
hazardous locations.
Specifications
These specifications are typical for –40 to 70 °C unless otherwise
noted. Specifications are subject to change without notice.
Output Characteristics
Number of channels..........................16
Output type .......................................Sinking
Voltage range ....................................5 to 30 VDC
Output impedance.............................0.12 Ω
(0.12 V drop at 1 A)
Maximum current
Per channel .................................2 A
All channels
FP-DO-403...........................16 A
2
cFP-DO-403.........................16 A
2
at –40to60 °C
12 A
2
at 60 to 70 °C
Maximum OFF state leakage............50 μA
Output delay time .............................50 μs
Physical Characteristics
Indicators .......................................... Green POWER and
READY indicators, 16 green
output state indicators
Weight
FP-DO-403.................................140 g (4.8 oz)
cFP-DO-403 ...............................110 g (3.7 oz)