National Instruments FP-RTD-122 Network Router User Manual


 
© National Instruments Corp. 13 FP-RTD-122 and cFP-RTD-122
Maximum altitude.............................2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered
Pollution Degree ..............................2
Shock and Vibration
These specifications apply only to the cFP-RTD-122.
NI recommends Compact FieldPoint if your application is subject
to shock and vibration.
Operating vibration, random
(IEC 60068-2-64)..............................10–500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27)..............................50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement,
control, and laboratory use:
IEC 61010-1, EN 61010-1
UL 3121-1, UL 61010C-1
CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to
the product label or to
ni.com.
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions..........................................EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Immunity...........................................EN 61326:1997 + A2:2001,
Table 1
Note For EMC compliance, operate this device with