Klinkmann Automation Omron Ethernet DAServer 42
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 17014m13
Memory Area Prefix
Tag
Type
Range Value
Range
Format
Suffix
IR & SR areas
(Bit status)(***)
IR
Discrete
IR0:00...IR255:15
or 0.00...255.15
0, 1
IR & SR areas
(Word contents) (***)
IR
Integer IR0...IR255
or 0...255
(*) u s b f g l
m d e c
Latching Relay area
(Bit status)
LR
Discrete
LR0:00... LR15:15
0, 1
Latching Relay area
(Word contents)
LR
Integer LR0... LR15 (*) u s b f g l
m d e c
Holding Relay area
(Bit status)
HR
Discrete
HR0:00... HR19:15
0, 1
Holding Relay area
(Word contents)
HR
Integer HR0... HR19 (*) u s b f g l
m d e c
Auxiliary Relay area
(Bit status)
AR
Discrete
AR0:00... AR23:15
0, 1
Auxiliary Relay area
(Word contents)
AR
Integer AR0... AR23 (*) u s b f g l
m d e c
Completion flags for
Timers/Counters(**)
TC
Discrete
TC0... TC255 0, 1
Present Values for
Timers/Counters
PV
Integer PV0... PV255 (*) u s b f g l
m d e c
Data Memory area
(Bit status) (****)
DM
Discrete
DM0:0...DM6655:15
0, 1
Data Memory area
(Word contents) (****)
DM
Integer DM0...
DM6655
(*) u s b f g l
m d e c
Item/point names, corresponding to IR and SR areas, may be without prefix.
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default
value range for Integer Tag Type is unsigned integer.
(**) Read only
(***) Addresses 50 to 199 in IR & SR area in CPM2A/CPM2C PLCs and 20 to 199 in IR &
SR area in CPM1/CPM1A/SRM1(-V2) PLCs are read only.
(****) Addresses DM1024 to DM6143 in CPM1/CPM1A PCs and DM2048 to DM6143 in
CPM2A/CPM2C/SRM1(-V2) PCs are read only.
The following examples show the correct format for item names for C/CPM2x PLCs:
IR2:01 - CIO area (Bit status), word address 2, bit number 1.
211 - CIO area (Word contents), word address 211.
LR62.10 - Latching Relay area (Bit status), word address 62, bit number 10.
DM21 - Data Memory area (Word contents), word address 21.