Klinkmann Automation Omron Ethernet DAServer 58
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 17014m13
number too large. number below the
maximum node number.
03 Send error caused by
lack of available space
in PLC internal buffers.
Reduce the traffic on the
Ethernet Unit. Check
user application.
DASProtFail
05 Node number setting
error.
Make sure the node
number is within
specified range and that
there are no duplicate
node numbers.
DASProtFail
06 Node number
duplication error.
Make sure that there are
no duplicate node
numbers.
DASProtFail
02: Remote
node error
01 IP address of remote
node was not set
correctly in IP address
table or IP router table.
Set IP address of remote
node into IP address
table, and, if
internetwork
transmission is required,
into IP router table.
DASProtFail
02 No node with the
specified unit address.
Check the remote
node’s unit address and
make sure the correct
one is being used in the
control data.
DASProtFail
05 Message packet was
corrupted by
transmission error or
response time-out
(response watchdog
timer interval too short)
or transmission frame
corrupted or PLC
internal reception buffer
full.
Check the protocol and
controller status by
reading them with FINS
commands. Increase the
number of transmit retry
attempts.
Increase the value for
the response monitor
time in the control data.
Read out the error log
and correct as required.
DASProtFail
03:
Communic.
Controller
error
01 Error occured in the
communications
controler. ERC
indicator is lit.
Take corrective action,
referring to
troubleshooting
procedures in PLC
manual.
DASProtFail
02 CPU error occured in
the PC at the
destination node.
Check the CPU
indicators at remote PLC
and clear the error in the
CPU (refer to the PLC’s
DASProtFail