Pelco C808M-G Switch User Manual


 
14 C808M-G (4/05)
COAXITRON CONTROL
To convert for use with a Coaxitron transmitter, do the following:
1. Convert the VS5004 to dual-monitor operation. Refer to Figure 8 and do the following:
a. Remove the cover.
b. Remove the rear panel of the chassis.
c. Remove the four screws attaching the PC board to the chassis.
d. Pull the PC board and rear panel assembly out of the chassis.
e. Turn the PC board over and rewire.
2. Convert to looping operation. Refer to Figure 5 and do the following:
NOTE:
Looping and terminated inputs may be mixed.
a. Locate the 75-ohm resistors located on the inside of the rear panel BNC jacks.
b. For each input to be looped, use wire cutters to clip one of the attached resistor leads.
c. Replace the cover.
3. Make all equipment connections. Refer to Figure 13 (VS5004) or Figure 14 (VS5008).
VS5004
The Coaxitron transmitter must be passive (nonamplified).
To operate a camera via Coaxitron signals, the corresponding channel switch must be in the MONITOR position.
VS5008
The Coaxitron transmitter must be active (amplified).
4. Make alarm connections if required. Refer to Figure 3 (VS5004) or Figure 4 (VS5008) and do the following:
VS5004
a.
Input:
Connect the alarm contact between the appropriate input (pins 1-4) and common (pin 5) on the 6-pin connector receptacle.
Pins 1 thru 4 correspond directly with the like-numbered front panel camera switches of the VS5004. The alarm output is an
open-collector NPN transistor. Current from the output to circuit ground should not exceed 600 mA.
b.
Output:
To activate an external device during an alarm, connect the device at pins 5 and 6 on the 6-pin connector.
VS5008
a. Input: Connect the alarm contact between the appropriate ALARM INPUT (terminals 1-8) and common (COM) terminal. The alarm
output is an open-collector NPN transistor. Current from the output to circuit ground should not exceed 40 mA.
b. Output: To activate an external device during an alarm, connect the device at the ALARM OUT terminal and the common (COM)
terminal.
5. Set the ALARM switch to the ON position.
NOTES:
When an alarm occurs, the monitor immediately switches to the alarmed channel, and the associated LED blinks. Multiple alarmed
channels sequence every five seconds (VS5004) or three seconds (VS5008). The alarm has priority over the MONITOR/AUTO/BYPASS
switch settings.
VS5008 with two-monitor configuration:
If a channel switch is set to the MONITOR position, Monitor 1 switches to the alarmed channel while Monitor 2 displays the selected
(MONITOR) channel.
If a channel switch is set to the BYPASS position, Monitor 1 switches to that channel if alarmed.
Once triggered, the alarm remains on until the input condition is removed or the ALARM switch is moved to the OFF position.
When in the ALARM switch is set to the OFF position, all alarm inputs are ignored.