Powerware 9170 Power Supply User Manual


 
UPS Startup
51
Powerware
®
9170 User's Guide S LTM-1344 B Uncontrolled Copy
Figure 41. Inserting the Modules
5. If you installed an optional battery cabinet, repeat Steps 1 and 2
to install the battery modules.
6. Reinstall the front covers.
7. Continue to the following section, Startup for Plug-Receptacle
Units" if your cabinet has a power cord already attached. If you
hardwired the UPS, skip to Startup for Hardwired Units" on
page 53.
Startup for Plug-Receptacle Units
To start a plug-receptacle unit, use the following steps:
1. Plug the power cable of the unit into an approved, functional
power outlet.
2. If external battery cabinets are installed, check the cable
connections between the UPS and external battery cabinets.
Close the DC disconnect switch on the back of each external
battery cabinet. Insert the switch key supplied with the cabinet
into the center of the switch button and turn clockwise
1/2-turn. Pull the button out to close the switch. Turn the key
back counter-clockwise, and remove the key.