Rackmount Solutions Enterprise Series Power Supply User Manual


 
15
English
SPECIFICATIONS
&
Acceptable input voltage
Input voltage (on-line operation)
Output voltage
Nominal input frequency
Input protection
Frequency limits (on-line operation)
Transfer time
Maximum load
On-battery output voltage
On-battery frequency
On-battery waveshape
Protection
Surge energy rating
(one time, 10/1000 us waveform)
Surge current capability
(one time, 8/20 us waveform)
Surge response time
Surge voltage let-through
(percentage of applied ANSI
C62.41 Cat. A +/-6kV test waveform)
Noise filter
Battery Type-Spill proof, maintenance free,
user replaceable, sealed lead-acid
Typical battery life
Typical recharge time
Operating temperature
Storage temperature
Operating and storage relative humidity
Operating elevation
Storage elevation
Electromagnetic immunity
Audible noise at 1 m (3 ft.)
Size (H x W x D) in Rackmount and
Desktop Configuration
Weight - Net (Shipping)
NOTE: 230Vac Specs Shown In ( ) 500VA 750VA 1100VA 1500VA 2300VA 3200 VA
Default 117 (225) Vac / User selectable at 108,113.117 (215,225,235) Vac
50 or 60 Hz, +/-.5 Hz, unless synchronized to utility during brownout
True Sine Wave
Overcurrent and short circuit protected, latching shutdown on overload
3 to 6 years, depending on the number of discharge cycles and ambient temp.
2 to 5 hours from total discharge
<5%
<1%
0 - 164 (0 - 290) Vac
75 - 164 (150 - 290) Vac
105 - 128 (210 - 250) Vac
50 or 60 Hz, autosensing
Resettable circuit breaker
50 or 60 Hz, +/-6Hz
<2 ms typical
500VA
300W
750VA
450W
1500VA
900W
2300VA
1380W
3200VA
1920W
500 J (440J)
6.5 kAmps total
500 J (440J)
13 kAmps total
0 ns (instantaneous) normal mode; <5 ns common mode
<5%
<0.5%
0 to 40 degrees C (+32 to 104 degrees F)
-15 to +45 degrees C (+5 to +113 degrees F)
0 to 95%, non-condensing
0 to +3,000 m (0 to + 10,000 ft)
0 to +15,000 m (0 to +50,000 ft)
IEC 801-2 level IV, 801-4 level IV, 801 -5 level III
<45 dBA
3.5 x 17 x 16"
(8.9 x 43.2 x 40.7) cm
5.25 x 17 x 16"
(13.4 x 43.2 x 40.7) cm
UL1778, CSA 22.1, CE EMC, CE SAFETY, TUV
Normal and common mode EMI/RFI suppression
Two 12 V
4.5 Ah
Two 12 V
7.2 Ah
10 Base-T surge protection
let-through (as a percentage of an
applied +/-6 kV 1.2/50 us, 500
Telephone line surge protection let-through
(as a percentage of an applied +/-6 kV
1.2/50 us, 500 a 8/20 us test)
Safety and approvals
EMC Verification
FCC Class B certified
Four 12 V
12 Ah
Four 12 V
4.5 Ah
1100VA
660W
Four 12 V
7.2 Ah
Four 12 V
12 Ah
43(49)lb 52(58)lb 57(62)lb 74(80)lb 88(94)lb 95(101)lb
19.5(22)Kg 23.5(26)Kg 25.5(28)Kg 33.5(36)Kg 40(42.5)Kg 43(45.5)Kg