Rackmount Solutions Enterprise Series Power Supply User Manual


 
16
Enterprise Series
Date of manufacture
1826
Enabled
Enabled
UPS output
Use this function to uniquely
identify the UPS in your net-
work configuration
Enter the current date when
replacing batteries
When enabled, the UPS will
automatically restart from a
low battery shutdown
when normal AC returns
Enabled - the UPS will emit
a short beep when in the
battery mode. At Low Bat-
tery the UPS will emit two
tones from low battery
warning until shutdown.
Disabled - Use only when
software is controlling the
UPS or to silence the alarm
UPS Output - When the UPS
is told to shut down, it turns
off the UPS output only. UPS
- Turns off the UPS which
requires the UPS to be
turned on manually
changes output voltage
during battery mode opera-
tions
(These items require optional software or hardware)
FUNCTION
FACTORY DEFAULT
DESCRIPTION
Up to 64 characters to
define the UPS
Date of battery re-
placement -
day/month/year
XX/XX/XXXX
Up to 5 characters
Enable or disable
Enabled, at low bat-
tery, disabled
UPS output or UPS
108, 113, 117Vac
(215, 225, 235)Vac
USER CHOICES
UPS ID
Battery install
date
Battery life in
days
Enable/
Disable auto
restart
Set audible
alarm state
Shutdown
Type
Set inverter
output voltage
At first battery replacement,
reset to reflect actual num-
ber of days experience in
your environment or leave
factory default.
117Vac
( 225)Vac
EnglishEnglish
CONFIGURABLE PARAMETERS
AND SETTINGS
'