5. EMI And Environmental Type Tests
RuggedCom® RuggedBackbone™ 32 RX5000 Installation Guide Rev106
5. EMI And Environmental Type Tests
Test Description Test Levels
Severity
Levels
Enclosure Contact +/- 8 kV 4
IEC 61000-4-2 ESD
Enclosure Air +/- 15 kV 4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m Note
a
Signal ports +/- 4kV @ 2.5kHz Note
a
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports +/- 4kV 4
Signal ports
+/- 4kV line-to-earth,
+/- 2kV line-to-line
4
D.C. Power ports
+/- 2kV line-to-earth,
+/- 1kV line-to-line
3IEC 61000-4-5 Surge
A.C. Power ports
+/- 4kV line-to-earth,
+/- 2kV line-to-line
4
Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
IEC 61000-4-6 Induced (Conducted) RFI
Earth ground ports 10V 3
40 A/m, continuous,
1000 A/m for 1 s
Note
a
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s 5
D.C. Power ports
30% for 0.1s, 60% for
0.1s, 100% for 0.05s
N/A
IEC 61000-4-29 Voltage Dips & Interrupts
A.C. Power ports 30% for 1 period, 60% for 50 periods N/A
IEC 61000-4-11 Voltage Dips & Interrupts A.C. Power ports
100% for 5 periods,
100% for 50 periods
N/A
Signal ports
2.5kV common, 1kV
diff. mode@1MHz
3
D.C. Power ports
2.5kV common, 1kV
diff. mode@1MHz
3IEC 61000-4-12 Damped Oscillatory
A.C. Power ports
2.5kV common, 1kV
diff. mode@1MHz
3
Signal ports 30V Continuous, 300V for 1s 4
IEC 61000-4-16 Mains Frequency Voltage
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17
Ripple on D.C.
Power Supply
D.C. Power ports 10% 3
Signal ports 2kVAC (Fail-Safe Relay output) N/A
D.C. Power ports 1.5kVDC N/AIEC 60255-5 Dielectric Strength
A.C. Power ports 2kVAC N/A
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/AIEC 60255-5 H.V. Impulse
A.C. Power ports 5kV N/A
a
RuggedCom-specified severity levels
Table 5.1. IEC 61850-3 EMI Type Tests