5. EMI And Environmental Type Tests
RuggedCom® RuggedBackbone™ 33 RX5000 Installation Guide Rev106
Test Description Test Levels
Enclosure Contact +/-2kV, +/-4kV, +/- 8kV
IEEE C37.90.3 ESD
Enclosure Air +/-4kV, +/-8kV, +/-15kV
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m
Signal ports +/- 4kV @ 2.5kHz
D.C. Power ports +/- 4kV
A.C. Power ports +/- 4kV
IEEE C37.90.1 Fast Transient
Earth ground ports +/- 4kV
Signal ports 2.5kV common mode @1MHz
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHzIEEE C37.90.1 Oscillatory
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz
Signal ports 5kV (Fail-Safe Relay output)
D.C. Power ports 5kVIEEE C37.90 H.V. Impulse
A.C. Power ports 5kV
Signal ports 2kVAC
D.C. Power ports 2kVDCIEEE C37.90 Dielectric Strength
A.C. Power ports 2kVAC
Table 5.2. IEEE 1613 (C37.90.x) EMI Immunity Type Tests
a
Test Description Test Levels
IEC 60068-2-1 Cold Temperature Test Ad -40°C, 16 Hours
IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing), 55°C , 6 cycles
IEC 60255-21-1 Vibration 2g @ (10 - 150) Hz
IEC 60255-21-2 Shock 30g @ 11mS
Table 5.3. Environmental Type Tests