Schneider Electric 170AMM11030 Network Card User Manual


 
31005009 01 November 2003 5
Specifications
Overview This section contains specifications for the 170AMM11030 Momentum I/O base.
General
Specifications
The following table contains general specifications for the I/O base. Each discrete
output is protected against short-circuiting and overload.
External Power Requirement
Normal Operating Voltage Range 16 to 42 VDC
Absolute Minimum Voltage 12 VDC
Absolute Maximum Voltage 45 VDC
Electrical
Module Current 400 mA at 24 VDC
EMC for Industrial Environment
Immunity IEC 1131-2
Surge on auxiliary power supply 500 V
Emissions EN 50081-2
ENV 50140 10 V/M
Agency Approvals UL, CSA, CE, FM Class 1, Div. 2 (pending)
Isolation
Discrete I/O point to discrete I/O point None
Field to ground 500 VAC
Field to communication adapter 500 VAC
Analog output channel to channel 700 VDC
Environmental
Storage Temperature -40 to 85° C
Operating Temperature 0 to 60° C
Humidity Operating 95% RH @ 60° C
Humidity Non-Operating 95% RH @ 60° C
Vibration Operating 10 - 57 HZ 0.075 MMDA
57 - 150 HZ 1 G
Shock Non-Operating 15 G, 11 MS, 3 shocks/axis
Free Fall (Unpackaged) 0.1 meter