The shutdown sequences take into account the time required for the registered servers to shut down
without losing data (see shutdown parameters ). Once the sequence has started, the commands are
disabled until it ends.
After a startup sequence, the commands are disabled for 120 seconds to enable the servers to fully restart
The Check column proposes six different commands, and a command is only actually started after clicking on
'Execute':
“Safe power down”: a sequence to switch off output power is launched immediately. The symbol representing
the output flashes, indicating that the sequence is in progress. The systems supplied are shut down correctly
while the shutdown sequence is running, then the output is cut.
“Safe power down & reboot”: A sequence to switch off then restore output power is launched immediately.
The symbol representing the output flashes, indicating that the shutdown sequence is in progress. The
powered systems are shut down correctly during the shutdown sequence, then the output is switched off.
Finally, the restart sequence is launched at the end of the time delay specified in the “Toggle duration”
parameter. The output status is updated.
Immediate On”: a sequence to switch on output power is launched immediately. The output is re-powered
and the systems supplied start up again correctly.
Delayed, safe power down”: this is the same switch off sequence as for the “ Safe power down ” command,
but postponed by the number of seconds programmed in the “Off Delay” parameter.
Delayed, safe power down & reboot:” this is the same switch off then on sequence as for the Safe power
down & reboot ” command, but postponed by the number of seconds programmed in the “ Off Delay
parameter.
Delayed On ”: this is the same switch on sequence as for the “ Immediate On ” command, but postponed by
the number of seconds programmed in the “ On Delay ” parameter.
The Save button saves the Off Delay, Toggle duration and On Delay parameters on the card .
Security: The administrator must click on Save and enter his login / password to save modifications or run
commands. The login and password by default are: MGEUPS.