1.7 Technical data
1.7.1 Configuration
The user can configure the card with one of the following means:
◗ Web browser
◗ Local serial link
◗ Telnet console
◗ BOOTP/DHCP
◗ Mupgrade
1.7.2 Administration
◗ Up to 50 workstations protected
◗ Up to 15 browsers connected at the same time
◗ E-mail sending configurable according to UPS alarms and transmission of a periodical report
◗ Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting
down the installation
◗ Control of UPS on/off switching via the HTML interface
◗ Adjustment and control Power via the HTML interface, sequential starting of the installation and
optimisation of backup time by shutting down non-priority systems
◗ Adjustment of date and time via NTP server - Daylight Saving Time management
◗ Protection by encrypted password.
◗ Protection by secured connection SSL and SSH
◗ Saving of logs in the non-volatile memory
◗ Automatic language detection according to browser configuration.
◗ Languages available: English / French / Spanish / German / Italian
◗ On-line help available for each page
◗ Card firmware updated via the network
◗ Card configuration deployment on your installed base through network utility (Mupgrade)
1.7.3 Network
◗ Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet
◗ SNMP trap port modifiable (by default = 162)
1.7.4 MIB (Management Information Base)
◗ MIB IETF UPS (RFC1628) for UPS
◗ MIB MGE V1.7 AD, for UPS
◗ MIB MGE V2.2 AA, for STS
1.7.5 Environment sensor
◗ Temperature measurement from 0 to 70 °C with +/- 1° C accuracy
◗ Measurement of humidity from 0 to 100 % with +/- 6 % accuracy
◗ Min / max time-stamped function for temperature and humidity
◗ Choice of temperature readings in Celsius or Fahrenheit
◗ High and low thresholds, hysteresis and offset adjustable via Web interface