Schneider Electric E4800 Network Router User Manual


 
930-112-01 PowerLogic
TM
E4800 Series
02/2009 PowerLogic E4800 configuration tool guide
© 2009 Schneider Electric All Rights Reserved
7
5. Restore power. When control power is restored, the meter will receive
an IP address from a local DHCP server. This IP address can be
viewed from the Diagnostics menu.
NOTE: To use a static IP address, have your local network
administrator assign the desired IP address to the MAC address of the
meter in the DHCP server configuration.
PowerLogic Configuration Tool The PowerLogic E4800 configuration tool is available on the CD shipped with
each unit, and is used to configure all programmable parameters listed in
Table 1.
Configuring the meter Use the following procedure to configure the meter.
1. Establish an Ethernet network connection with the meter using one of
the methods descirbed in “Communications Connections” on page 5.
2. Ensure the programming switches are in the ON position. The
programming switches are two-position DIP switches labeled SW1, and
are located inside the meter cover below the Display button. To enable
meter configuration, both switches must be physically set to the ON
position. When both switches are in the OFF position, meter
configuration is disabled.
3. Start the configuration tool by entering “PowerLogic” as the User
Name, and “E4800” as the Password (see Figure 1). Click Ok.
Figure 2: Login screen