To change the current rating for all meter points assigned to a meter:
1. Select a meter from the Meter Points (Circuits) List. The selected
meter will appear in the Name field of the middle pane. See Figure 10.
2. In the Alter Current for Probes pane, enter the desired value
referenced to the CT primary rating in the Current field, and click on
Change Probes in Selected Meter.
To change the current rating for all meter points assigned to all meters:
1. In the Alter Current for Probes pane, enter the desired value
referenced to the CT primary rating in the Current field, and click on
Change all Probes in all Meters. See Figure 10.
Badge Numbering
Each meter point can be configured with a name defined by the user. The
meter point name, known as the badge number, can be 13 alphanumeric
characters in length. The Badge Numbering pane allows the user to set two
types of badge numbers:
sequential, which assigns a badge number to each meter point after the
prefix (for example CORP-00000001 to CORP-00000012)
grouped by meter, which uses a base prefix to designate the meter,
then assigns a sequential badge number suffix to each meter point
assigned to that meter (for example CORP-00001-01 to
CORP-00001-12)
The configuration tool provides examples before the badge number is
assigned to the meter. In the Badge Numbering pane shown in Figure 11,
the following fields and buttons are provided for assigning badge numbers:
Prefix field - an alphanumeric field that prefixes the number field
Badge Number field - a numeric field that becomes part of the prefix
for meter points assigned to that meter, or the first number in the
sequence to be assigned to individual meter points
Incremental badge numbers button - choosing this button assigns a
sequential badge number for each meter point
Single badge number button - choosing this button assigns one badge
number prefix followed by a numeric suffix for each meter point
assigned to that meter