Toshiba 1700 Power Supply User Manual


 
Standard Module Connections (cont’d)
If two modules are to be stacked on top of each other, they should
be interlocked to reduce the chances of the top module being
knocked over. Modules do not have to be stacked for the system to
operate. The following steps will guide the user through the process
of assembling and connecting the modules.
Step 1: Place the electronics module on top of
the battery module so that the six round feet on
the bottom of the electronics module fit into the
matching keyhole slots on the top of the battery
module.
Step 2: Slide the
upper unit forward.
This will cause the
two units to lock
together. In order to unlock the units, lift
up on the top module, and slide it back.
This will release the interlock (figure 3).
Step 3: Connect the input power cord
(figure 4) to the AC power source. If no
AC power source is available go to step 5.
Step 4: Switch the input
breaker to the on position
(figure 1, page 9). Please note
that a battery fault will occur.
Step 5: Plug the battery cord
coming from the battery pack
into the blue battery plug
located on the back of the
electronics module (figure 4).
This will clear the fault from
step 4. Attention: If the
battery cord is not plugged into
the battery plug the UPS will
not be able to provide backup
power in the event of a loss of AC input power.
Figure 3
Module Interlock
CAUTION Battery modules present a lifting hazard. The
battery module for this unit weighs approximately 60 lbs.
Two person lift is required to avoid injury.
Figure 4
Power Connections