Toshiba 300 KW Power Supply User Manual


 
44
G8000 Series Installation and Operation Manual
12.2 Mechanical Specication (cont.)
Nominal Capacity 150 kW 225 kW 300 kW
Cabinet Protection
Conformity
IEC298 IP20*
Exterior Paint Sherwin Williams, HHT2-7055, 079 Beige Texture
Panel Thickness
FRONT: 1/16 in. (1.6 mm)
BACK/SIDE/TOP: 3/64 in. (1.2 mm)
BOTTOM: 1/8 in. (3.2 mm)
Input/Output
Cabling Entrance
TOP and BOTTOM TOP
Ground/Control
Wiring Entrance
TOP and BOTTOM TOP
Outline Dimension
W: 55.1 in. (1400 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
W: 76.8 in. (1951 mm)
D: 31.8 in. (808 mm)
H: 79.4 in. (2017 mm)
Unit Weight 2467 lbs (1119 kg) 2980 lbs (1352 kg) 4575 lbs (2075 kg)
Shipping Weight 2556 lbs (1159 kg) 3069 lbs (1392 kg) 4725 lbs (2143 kg)
Floor Loading Per
Footprint
3280 lbs/ft
2
(16,014 kg/m
2
)
3733 lbs/ft
2
(18,226 kg/m
2
)
2460 lbs/ft
2
(12,011 kg/m
2
)
Clearance
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection
51,182 BTU/h
(12,897 kcal/h)
68,243 BTU/h
(17,197 kcal/h)
68,243 BTU/h
(17,197 kcal/h)
*IP20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UPS.